OCR: BURGER Rebuilding for Profit A cooling tower can be an untapped profit center for energy conservation and improved production. More often than not, the limiting factor of production is the quality (degree of coldness) of the water used in the production processes. This section illustrates , using real world examples , the before and after conditions of different types of optimized towers. EXAMPLE #6 - COGENERATION PLANT Before After 20,750 GPM 20,750 102 F HWT 102 F 87 F CWT 83 F 71 F WBT 71 F 16 F Approach 13F Plastic wire fill removed and replaced with Super Cellular non clogging fill . Testing certified tower to be 99.2 % of capability which improved vacuum 3/4 inch. $98,000 expense with projected payback in 14 months. - END OF SECTION - 1 Continue 2 Previous 0 Main Menu